Power Quality
Poor power quality costs millions in damage and penalties. Monitor it proactively.
Key Metrics
127th
Harmonics Order
50K
Events Captured
64
Samples/cycle
EN50160
Compliant
Why This Matters
Voltage Quality Is an Equipment-Lifetime Problem
Power quality describes how closely the delivered voltage matches a clean, stable sine wave. In practice, it is almost never clean: variable-speed drives, rectifiers, and switching power supplies all distort the waveform, and the grid itself injects sags, swells, and transients. The cost is paid in heat, derating, and premature failure of motors, transformers, and electronics.
The financial exposure is larger than most facilities teams assume. Harmonic current flowing through neutrals and transformers heats them, wasting energy and reducing the capacity of distribution equipment. Voltage sags - the most common power quality event - cause nuisance trips of process equipment and IT that can cost far more than the energy involved. In continuous-process industries, a single sag that stops a line can wipe out a year of electricity savings.
The point of monitoring is not to achieve a perfect waveform - that is impossible. It is to quantify the level of disturbance, catch the damaging events, and demonstrate compliance where utility or tenant agreements require it.
Standards
The Reference Frameworks
Limits on voltage and current harmonics at the point of common coupling, the standard for industrial harmonic compliance
European voltage characteristics standard covering frequency, magnitude, harmonics, and interruptions
Defines measurement methods and accuracy classes for power quality instrumentation
Measurement technique for harmonics and interharmonics, referenced by IEEE 519 assessments
Deep Dive
Harmonics: The Steady-State Distortion
Harmonics are current or voltage components at integer multiples of the fundamental 50/60 Hz frequency. A variable-speed drive's rectifier stage draws current in pulses rather than smoothly, which produces 3rd, 5th, 7th, and higher harmonics. The 3rd harmonic is particularly problematic in three-phase systems because triplen harmonics (orders divisible by three) add in the neutral conductor, overheating a neutral that was never sized for full load current.
5%
IEEE 519 voltage THD limit most commonly applied at the service point (for <69kV systems)
3rd
Harmonic order that adds in the neutral and overloads shared neutrals
10-15%
Typical transformer derating observed with unfiltered nonlinear loads
Mitigation options are well established: line reactors and harmonic-rated drives reduce low-order current at the source, passive filters trap specific harmonics, and active filters cancel distortion dynamically. The correct choice depends on measured levels, not assumptions - which is exactly why monitoring comes first.
Deep Dive
Sags, Swells, and Transients: The Event Family
Where harmonics are a continuous condition, sags, swells, and transients are discrete events that must be captured at high resolution to be understood. A sag is a voltage dip typically lasting a few cycles to a few seconds - caused by large motor starts or grid faults elsewhere. A swell is the opposite, and a transient is a short, high-energy spike or notch lasting microseconds to a few milliseconds. None is visible to a standard utility meter, which is why dedicated PQ analysis is required.
| Event | Definition | Common Cause | Typical Impact |
|---|---|---|---|
| Voltage sag | RMS voltage drops 10-90% for 0.5 cycle to 60s | Motor starting, grid faults, transformer switching | IT resets, process trips, contactor dropout |
| Voltage swell | RMS voltage rises 110-180% for 0.5 cycle to 60s | Single-phase faults elsewhere, load shedding | Power supply stress, electronic damage |
| Transient | Short voltage spike or notch, microseconds to ms | Lightning, switching, capacitor banks, VFD commutation | Silicon damage, nuisance alarms, data corruption |
| Interruption | Supply below 10% for longer than 60s | Protection operation, grid incidents | Full load loss, restart costs, process loss |
Capturing these events requires instrumentation with waveform sampling - typically 128 samples per cycle or better - and event-triggered recording. The value is correlation: when a process trips, the PQ log shows whether the trip followed a sag or transient, converting a mystery into a root cause.
Best Practices
Designing a Power Quality Monitoring Plan
The goal of a PQ monitoring plan is not maximum instrumentation but targeted visibility at the points where compliance is judged and damage is felt.
Step 1
Measure at Boundaries
Instrument the utility service point and each transformer feeding critical or nonlinear loads. IEEE 519 compliance is assessed at the point of common coupling.
Step 2
Match Accuracy to Need
Use revenue-grade meters (IEC 61000-4-30 Class A) where compliance evidence matters; lower classes only where you need trend, not proof.
Step 3
Baseline Three Months
A quarterly baseline captures seasonal load shifts and reveals the recurring harmonic profile before any mitigation spend is approved.
Step 4
Correlate to Events
Join PQ logs with production, IT, and equipment-failure records so each captured event is tied to a consequence and a cost.
Evaluation Checklist
- Confirm the instrument captures full waveforms, not just RMS summaries, for event analysis
- Define IEEE 519 evaluation criteria per site before monitoring starts
- Log sag thresholds tuned to your sensitive loads' actual immunity curves, not generic defaults
- Verify data retention spans a full year so seasonal harmonics and utility incidents are captured
Protect Your Equipment from Power Disturbances
Talk to our power quality engineers about instrumenting your service entrance and critical loads.
Get Started